BBA-160RT BROADBAND SERIES SPECIFICATIONS

FEATURES

·         Flame-arresting one-way pressure-relief vent for safety and long life.

·         Case and cover of high-impact polypropylene with reinforced endwalls to reduce bulging.

·         Thermally welded case-to-cover bond to ensure a leak-proof seal.

·         Absorbent Glass Mat (AGM) technology for efficient gas recombination of up to 99% and freedom from electrolyte maintenance.

·         Thick positive plate design for maximum service life.

·         UL-recognized component.

·         Multicell design for ease of installation and maintenance.

 

·         Removable carrying handles.

·         Not restricted for air transport  - Complies with IATA/ICAO Special Provision A67.

·         Not restricted for surface transport – Classified as non-hazardous material as related to DOT-CFR Title 49 parts 171-189.

·         Not restricted for water transport- Classified as non-hazardous material per IMDG Amendment 27.

·         Gas recombination efficiency of up to 99% for freedom from electrolyte maintenance.

·         Can be used in any orientation. Upright, side or end mounting recommended.

 



Cells Per Unit

Voltage Per Unit

Weight

Electrolyte   

Maximum Discharge Current

Short Circuit Current

Ohms Imped. 60 Hz (W)

Dimensions Overall (Inches)

     6

12.84

62.0 lbs.

28.0 kg. 

Absorbed H2SO4

SG = 1.300

800 Amps

3300 Amps @ 0.1 sec.

0.0040 Ohms

Length = 12.51 Width   = 6.83   Height  = 9.05


Capacity

88 Ah @ 20 hr. rate to 1.75 volts per cell @ 77°F (25°C)                      

 

Operating Temperature Range

Discharge; -40°F (-40°C)  to +160°F (71°C), Charge; -10°F (-23°C) to +140°F (60°C) (with temperature compensation)

Nominal Operating Temperature Range

+74°F (23°C) to +80°F (27°C)

Float Charging Voltage

13.5 to 13.8 VDC / unit Average @ 77°F (25°C)

Recommended Maximum Charging Current Limit

C/5 amperes (17.6 amperes @ 100% depth of discharge) @ 20 hour rate

Maximum AC Ripple (Charger)

0.5% RMS or 1.5% P-P of float charge voltage recommended for best  results. 

Maximum voltage allowed = 1.4% RMS (4% P–P)

Maximum current allowed = 4.4 amperes RMS (C/20)

Self Discharge

Dynasty Broadband batteries may be stored for up to 6 months at 77°F (25°C) and then a freshening charge is required.  For higher temperatures the time interval will be shorter.

Accessories

Inter unit connectors, racks and cabinet systems are available.

Terminal

Flag terminal with 0.28” clearance hole to accept 0.25” ( 6mm ).

Terminal Hardware Initial Torque

65 in.-lbs. (7.4 N-m).

Terminal Hardware Annual Retorque

52 in. – lbs. (5.8 N–m).


12 Volts – 88 Ampere Hour Capacity @ 20 Hour Rate

Ampere Hour Capacity to 1.75 Volts per Cell @ 77°F (25°C)

Discharge in Hours

0.25

0.50

1.00

2.00

3.00

4.00

5.00

6.00

7.00

8.00

10.0

12.0

20.0

24.0

48.0

72.0

100

Amp-Hr Capacity

35.9

45.2

54.3

62.0

67.6

71.0

74.0

76.0

77.5

79.0

81.4

83.6

88.0

88.4

89.8

90.9

92.0


Constant Current Discharge Ratings

Ampere Hour Capacity to 1.75 Volts per Cell @ 77°F ( 25°C )

Amperes

5

10

15

20

25

30

35

40

45

50

Run Time (min)

1042

475

295

208

160

125

103

87

75

66


Constant Current Discharge Ratings – Amperes @ 77°F (25°C)

Operating Time to End Point Voltage (in hours)

End Point Volts/Cell

0.25

0.50

1.00

2.00

3.00

4.00

5.00

6.00

7.00

8.00

10.0

12.0

20.0

24.0

48.0

72.0

100.0

1.75

144

90.0

54.3

31.0

22.5

17.8

14.8

12.7

11.1

9.90

8.14

6.97

4.40

3.68

1.87

1.26

0.92

1.80

132

85.0

51.0

30.3

22.0

17.3

14.4

12.3

10.8

9.60

7.98

6.75

4.30

3.61

1.85

1.25

0.90

1.85

120

77.0

47.7

28.2

20.5

16.2

13.5

11.6

10.2

9.10

7.60

6.50

4.11

3.45

1.78

1.20

0.87

1.90

101

68.0

41.4

25.4

18.5

14.7

12.3

10.6

9.30

8.40

6.95

5.93

3.83

3.24

1.63

1.11

0.81


Note:  Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation.  Specifications subject to change without notification.