Clear Power Solutions

Providing The Power You Need!

About Us | Contact Us

Telecommunications Power Installation Solar Panel Installation
Home Batteries Solar Wind Services

BBG-180RT BROADBAND SERIES SPECIFICATIONS

FEATURES

·         Flame-arresting one-way pressure-relief vent for safety and long life.

·         Case and cover of high-impact polypropylene with reinforced endwalls to reduce bulging.

·         Thermally welded case-to-cover bond to ensure a leak-proof seal.

·         Complies with UN 2794

·         Thick positive plate design for maximum service life.

·         UL-recognized component.

·         Multicell design for ease of installation and maintenance.

 

·         Designed to meet full published ratings at initial start-up installation.

·         Not restricted for surface transport – Classified as non-hazardous material as related to DOT-CFR Title 49 parts 171-189.

·         Gelled electrolyte for superior float service life and thermal mangement.

·         Gas recombination efficiency of up to 99% for freedom from electrolyte maintenance.

·         Can be used in any orientation. Upright, side or end mounting recommended.

 


Cells Per Unit

Voltage Per Unit

Weight

Electrolyte 

Maximum Discharge Current

Short Circuit Current

Ohms Imped. 60 Hz (W)

Dimensions Overall (Inches)

     6

12.84

66.0 lbs.  

30.0 kg. 

Gelled H2SO4

SG = 1.300

900 Amps

2500 Amps @ 0.1 sec.

0.0050 Ohms

Length = 13.42 Width = 6.80  Height  = 9.48


Capacity

93.6 Ah @ 20 hr. rate to 1.75 volts per cell @ 77°F (25°C)                      

 

Operating Temperature Range

Discharge; -40°F (-40°C)  to +160°F (71°C), Charge; -10°F (-23°C) to +140°F (60°C) (with temperature compensation)

Nominal Operating Temperature Range

+74°F (23°C) to +80°F (27°C)

Float Charging Voltage

13.5 to 13.8 VDC / unit Average @ 77°F (25°C)

Recommended Maximum Charging Current Limit

C/5 amperes (18.7 amperes @ 100% depth of discharge) @ 20 hour rate

Maximum AC Ripple (Charger)

0.5% RMS or 1.5% P-P of float charge voltage recommended for best  results. 

Maximum voltage allowed = 1.4% RMS (4% P–P)

Maximum current allowed = 4.6 amperes RMS (C/20)

Self Discharge

Dynasty Broadband batteries may be stored for up to 6 months at 77°F (25°C) and then a freshening charge is required.  For higher temperatures the time interval will be shorter.

Accessories

Inter unit connectors, racks and cabinet systems are available.

Terminal

Flag terminal with 0.28” clearance hole to accept 0.25” ( 6mm ).

Terminal Hardware Initial Torque

65 in.-lbs. (7.4 N-m).

Terminal Hardware Annual Retorque

52 in. – lbs. (5.8 N–m).


12 Volts – 94 Ampere Hour Capacity @ 20 Hour Rate

Ampere Hour Capacity to 1.75 Volts per Cell @ 77°F (25°C)

Discharge in Hours

0.25

0.50

1.00

2.00

3.00

4.00

5.00

6.00

7.00

8.00

10.0

12.0

20.0

24.0

48.0

72.0

100

Amp-Hr Capacity

39.5

50.5

61.2

70.4

75.6

78.8

82.0

83.4

85.4

86.4

88.9

89.9

93.6

95.0

99.8

102

103


Constant Current Discharge Ratings

Ampere Hour Capacity to 1.75 Volts per Cell @ 77°F ( 25°C )

Amperes

5

10

15

20

25

30

35

40

45

50

Run Time (min)

1118

524

331

237

182

146

121

102

88

78


Constant Current Discharge Ratings – Amperes @ 77°F (25°C)

Operating Time to End Point Voltage (in hours)

End Point Volts/Cell

0.25

0.50

1.00

2.00

3.00

4.00

5.00

6.00

7.00

8.00

10.0

12.0

20.0

24.0

48.0

72.0

100.0

1.75

158

101

61.2

35.2

25.2

19.7

16.4

13.9

12.2

10.8

8.89

7.49

4.68

3.96

2.08

1.42

1.03

1.80

145

95.7

59.4

34.6

24.8

19.5

16.2

13.8

12.0

10.7

8.78

7.40

4.62

3.90

2.04

1.39

1.02

1.85

127

87.5

56.0

33.2

24.0

18.9

15.7

13.3

11.7

10.4

8.51

7.17

4.46

3.77

1.97

1.34

0.98

1.90

107

75.6

50.0

30.5

22.2

17.6

14.6

12.5

10.9

9.71

7.96

6.70

4.16

3.51

1.82

1.23

0.09


Note:  Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation.  Specifications subject to change without notification.

The above information is the property of C&D Technologies, Inc. DYNASTY Division.


 

Home | Batteries | Solar | Wind | Services | Contact Us
2009 Clear Power Solutions, All Rights Reserved