Clear Power Solutions

Providing The Power You Need!

About Us | Contact Us

Telecommunications Power Installation Solar Panel Installation
Home Batteries Solar Wind Services

MPS12-100 MULTI PURPOSE SERIES SPECIFICATIONS

FEATURES

·         Flame-arresting one-way pressure-relief vent for safety and long life.

·         Thermally welded case-to-cover bond to eliminate leakage.

·         Absorbent Glass Mat (AGM) technology for efficient gas recombination of up to 99% and freedom from electrolyte maintenance.

·         Robust plate for extended life.

·         UL-recognized component.

·         Multicell design for economy of installation and maintenance.

·         Durable polypropylene container & cover.

 

·         Can be mounted in any orientation.

·         Not restricted for air transport  - Complies with IATA/ICAO Special Provision A67.

·         Not restricted for surface transport – Classified as non-hazardous material as related to DOT-CFR Title 49 parts 171-189.

·         Not restricted for water transport- classified as non- hazardous material per IMDG Amendment 27.

·         Computer designed lead, low calcium alloy grid for minimal gassing and ease of recycling.

 


Cells Per Unit

Voltage Per Unit

Weight

  Electrolyte                                     

Maximum Discharge Current

Short Circuit Current

Ohms Imped. 60 Hz (W)

Dimensions Overall (Inches)

     6

12.84

72.0 lbs.          

32.5 kg. 

Absorbed H2SO4

SG = 1.300

800 Amps

3600 Amps @ 0.1 sec.

0.0035 Ohms

Length = 13.42

Width   = 6.80

Height  = 9.48


Capacity

330 watts per cell at the 15 minute rate to 1.67 volts per cell @ 77ºF (25ºC).

100 Ah @ 20 hr. rate to 1.75 volts per cell @ 77°F (25°C)                      

86.2 Ah @ 10 hr. rate to 1.80 volts per cell @ 20°C (68°F)

Operating Temperature Range

Discharge; -40°F (-40°C)  to +160°F (71°C), Charge; -10°F (-23°C) to +140°F (60°C) (with temperature compensation)

Nominal Operating Temperature Range

+74°F (23°C) to +80°F (27°C)

Float Charging Voltage

13.5 to 13.8 VDC / unit Average @ 77°F (25°C)

Recommended Maximum Charging Current Limit

C/5 amperes (20.0 amperes @ 100% depth of discharge) @ 20 hour rate

Equalization and Cycle Service Charging Voltage

14.4 to 14.8 VDC/unit Average at 77ºF (25ºC).

Maximum AC Ripple (Charger)

0.5% RMS or 1.5% P-P of float charge voltage recommended for best  results. 

Maximum voltage allowed = 1.4% RMS (4% P–P)

Maximum current allowed = 5.0 amperes RMS (C/20)

Self Discharge

Dynasty MPS batteries may be stored for up to 6 months at 77°F (25°C) and then a freshening charge is required.  For higher temperatures the time interval will be shorter.

Accessories

Inter unit connectors, racks and cabinet systems are available.

Terminal

“ L “ terminal with 0.28” clearance hole to accept 0.25” ( 6 mm ) bolt.

Terminal Hardware Initial Torque

65 in.-lbs. (7.35 N-m).

Terminal Hardware Annual Retorque

52 in. – lbs. (5.88 N–m).


12 Volts – 100 Amperes Hour Capacity @ 20 Hour Rate

Ampere Hour Capacity to 1.75 Volts per Cell @ 77°F ( 25°C )

Discharge in Hours

1.00

2.00

3.00

4.00

5.00

6.00

7.00

8.00

10.0

12.0

20.0

24.0

72.0

100

Amp-Hr Capacity

61.5

69.5

75.0

78.3

81.0

84.0

86.0

88.0

90.8

93.5

100

100.5

103

104


Constant Power Discharge Ratings – Watts Per Cell @ 77ºF (25ºC)

Operating Time to End Point Voltage (in minutes)

End Point Volts/Cell

5

10

15

20

30

40

45

50

60

90

1.75

510

375

305

260

200

163

150

138

120

84.0

1.70

540

400

320

267

205

168

155

141

121

85.0

1.67

565

420

330

275

208

170

157

143

123

87.0

1.65

570

424

333

277

209

171

158

144

124

88.0

1.60

590

435

345

285

212

173

160

146

125

89.0


Constant Current Discharge Ratings – Amperes @ 77°F (25°C)

Operating Time to End Point Voltage (in hours)

End Point Volts/Cell

.083

.25

.50

.75

1

2

3

5

8

10

12

20

24

72

100

1.90

156

110

75.0

61.0

47.0

28.9

21.0

14.0

9.50

7.90

6.73

4.34

3.65

1.26

0.91

1.85

203

136

92.0

73.5

55.0

31.4

22.8

15.0

10.1

8.44

7.23

4.67

3.92

1.37

0.99

1.80

240

151

99.0

79.5

60.1

34.0

24.2

15.8

10.7

8.80

7.58

4.89

4.10

1.42

1.03

1.75

274

162

105

83.2

61.5

34.8

25.0

16.2

11.0

9.08

7.79

5.00

4.19

1.43

1.04

 

Note:  Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation.  Specifications subject to change without notification.

The above information is the property of C&D Technologies, Inc. DYNASTY Division.

 

 

 

 

 

Home | Batteries | Solar | Wind | Services | Contact Us
2009 Clear Power Solutions, All Rights Reserved