Clear Power Solutions

Providing The Power You Need!

About Us | Contact Us

Telecommunications Power Installation Solar Panel Installation

TEL12-105F Long Duration Series Specifications

FEATURES

·         Flame-arresting one-way pressure-relief vent for safety and long life.

·         Thermally welded case-to-cover bond to ensure a leak-proof seal.

·         Flame-retardant polypropylene case and cover compliant with UL94V-0 with an Oxygen Limiting Index of greater than 28.

·         Absorbent Glass Mat (AGM) technology for efficient gas recombination 99% plus.

·         Front accessible threaded copper alloy terminals for ease of assembly and reduced maintenance.

·         Thick positive plate design for maximum service float life – 10 year design life.

·         Complies with UL1778, 924, 1989 and 94 V-0.

·         UL-recognized component.

·         Battery design allows for 48VDC configuration in a standard 23” relay rack in less than 10” height.

·         Multicell design for ease of installation and maintenance.

·         Not restricted for air transport  - Complies with IATA/ICAO Special Provision A67.

·         Not restricted for surface transport – classified as non-hazardous material as related to DOT-CFR Title 49 parts 171-189.

·         Not restricted for water transport – classified as non-hazardous material per IMDG Amendment 27.

·         Minimizes battery interconnection cost and resistance with supplied copper connectors.


 

Cells Per Unit

Voltage Per Unit

Weight

  Electrolyte    

Maximum Discharge Current

Short Circuit Current

Ohms Imped. 60 Hz (W)

Dimensions Overall (Inches)

     6

12.84

80.0 lbs. 36.29 kg

Absorbed H2SO4

SG = 1.300

800 Amps

4000 Amps @ 0.1 sec.

0.0030 Ohms

Length = 22.59 Width = 4.98 Height  = 9.03


 

Capacity

100 Ah @ 8 hour rate to 1.75 volts per cell @ 77°F (25°C)                      

98.1 Ah @ 10 hour rate to 1.80 volts per cell @ 20°C (68°F)

Operating Temperature Range

Discharge; -40°F (-40°C)  to +140°F (60°C), Charge; -4°F (-20°C) to +122°F (50°C)

Nominal Operating Temperature Range

+74°F (23°C) to +80°F (27°C)

Float Charging Voltage

13.5 to 13.8 VDC / unit Average @ 77°F (25°C)

Recommended Maximum Charging Current Limit

C/5 amperes (21.8 amps @ 100% depth of discharge)

Maximum AC Ripple (Charger)

0.5% R M S or 1.5% P - P of float charge voltage recommended for best results. 

Maximum voltage allowed = 4% P – P

Maximum current allowed = 5.45 amperes R M S (C/20)

Self Discharge

Dynasty Telecom batteries may be stored for up to 6 months at 77°F (25°C) and then a freshening charge is required.  For higher temperatures the time interval will be shorter.

Accessories

Inter unit connectors, racks and cabinet systems are available.

Terminal

Threaded copper alloy insert terminal to accept 1/4 – 20 U N F bolt.

Terminal Hardware Torque

110 in. – lbs. (12.4 n – m).


 

12 Volts – 100 Ampere Hour Capacity @ 8 Hour Rate

Discharge in Hours

1.00

2.00

3.00

4.00

5.00

6.00

7.00

8.00

10.00

12.00

20.00

24.00

72.00

100.00

Amp-Hr Capacity

66.3

77.6

84.6

89.2

92.5

95.4

98.0

100

102

104

109

110

117

119


 

Note:  Batteries to be mounted with 0.5 in. spacing minimum and free air ventilation.

The above information is the property of Dynasty Specialty Battery Division.

 

 

 

 

 